Restore Defaults Sub-Menu (Reloading the Configuration Package Stored in the ACU+ Controller)
See also “Reloading the Configuration Package Stored in the ACU+ Controller” on page 29.
This procedure is typically used to restore any changes you made to the relay assignments, alarm severities, signal names, or PLC
expressions. This file is not shipped with the system. There are one or two steps required to restore your ACU+ as shipped.
• One step to reload the ACU+ configuration package (required only if you made any changes to relay assignments, alarm
severities, signal names, or PLC expressions).
• One step to reload the "SettingParam.run" file (required only if you made any setting changes like float/ equalize voltage or
alarm thresholds).
Your system may have been configured for specific options at the factory which creates a “SettingParam.run” file. Reloading the
configuration (restoring defaults) will return the system to the settings of the default configuration package. These are the
settings before specific options may have been configured by the factory. To restore the system to the settings as shipped, after
reloading the configuration (restoring defaults), you must reload the factory provided “SettingParam.run” file.
Note:
If a system was shipped with factory modified settings, the system is supplied with a USB memory device that contains a
“SettingParam.run” file as shipped. The “SettingParam.run” file has a seven-digit UIN (Unique Identification Number) preceding the
“SettingParam.run” filename. The UIN identifies a “SettingParam.run” file for use with a specific system. This file can be used to
restore your system to the configuration as shipped. Refer to “Reloading a Backed-Up ACU+ Configuration” on page 27 to reload the
supplied “SettingParam.run” file.
PROCEDURE
WARNING! When this procedure is performed, the Controller’s existing configuration and parameter settings will be lost. The
“SettingParam.run” file is deleted. Before reloading the configuration (restoring defaults), if you have made changes to any
setting save the “SettingParam.run” file or if you have made any name changes, relay assignments, alarm severities, or PLC
expressions save the configuration package (see Backing Up the ACU+ Configuration on page 26).
AFTER PERFORMING THIS PROCEDURE, RELOAD THE “SETTINGPARAM.RUN” FILE AND CONFIGURATION PACKAGE, IF REQUIRED.
Click on the “Restore Defaults” button. Click “OK” to confirm to overwrite the existing configuration package in memory with the stored
configuration package. The controller will automatically reboot. All settings WILL BE restored to the defaults of the stored configuration
package.
Note:
After rebooting, you must exit your browser and re-login to see any changes made.
Warning