"SMTemp Group" Parameter Settings:
Clr SMTemp Lost*:
Clears an SMTemp lost alarm.
SMTEMP # MENU
Menu Navigation:
Main Menu / Manual / SMTemp / SMTemp #
Note: For WEB Interface; menu items are found under Device
Information / SM Temp Group / SM Temp # / Control Tab.
"SMTemp #" Parameter Settings:
Clr Probe Alm*:
Clears an SMTemp probe fail alarm.
Quick Setting Menu
Auto/Manual
AUTO/MANUAL MENU
Menu Navigation:
Main Menu / Quick Setting / "Auto/Manual"
Note: For WEB Interface; menu items are found under Quick
Settings / “Auto/Manual Setting”.
"Auto/Manual" Parameter Settings:
Auto/Man State
Auto:
The Controller automatically controls the
power system.
Manual:
A User can manually change certain power
system control settings via the Manual menu. (See
Manual Menuon page 96.) This provides a
convenient means of making temporary adjustment
changes for testing purposes.
ECO Mode Set
ECO MODE SET MENU
Menu Navigation:
Main Menu / Quick Setting / ECO Mode Set
Note: For WEB Interface; menu items are found under Quick
Settings / “ECO Mode Setting.
"ECO Mode Set" Parameter Settings:
ECO Mode:
Enables or disables the Energy Optimization
Mode feature for all rectifiers. When enabled, the
following parameters can be set.
Energy Save Pt:
Energy Optimization is disabled if
the load is greater than this setting.
Best Oper Point:
Percent of full load capacity that the
rectifiers operate under in the Energy Optimization
mode.
Fluct Range:
If load fluctuation is less than this value,
rectifiers are not turned on or off for Energy
Optimization.
Cycle Period:
This is the time period that rectifiers
are turned on and off to maintain an equal operating
time for all rectifiers in the system.
Rects ON Time:
Time all rectifiers are turned on at
End of Cycle.
Turn Off Delay:
When the Energy Optimization
feature determines a rectifier can be switched off,
this is the time delay before the rectifier is switched
off.
FLT/EQ Volts
FLT/EQ VOLTS MENU
Menu Navigation:
Main Menu / Quick Setting / “FLT/EQ Voltag”
Note: For WEB Interface; menu items are found under Quick
Settings / “Float/Equalize Charge Voltage”.
"FLT/EQ Volts" Parameter Settings:
Float Voltage:
Float Charge output voltage setting.
EQ Voltage:
Equalize Charge output voltage setting.
FLT/EQ Set
FLT/EQ SET MENU
Menu Navigation:
Main Menu / Quick Setting / "FLT/EQ Set"
Note: For WEB Interface; menu items are found under Quick
Settings / “Float/Equalize Settings”.
"FLT/EQ Set" Parameter Settings:
Auto EQ:
Enables or disables the Automatic Equalize
Charge feature. When enabled, the following parameters
can be set.
EQ Start Curr:
The system is transferred to Equalize
Charge mode when battery charge current increases
to this setting. For example, a value of 0.060C10
means that an Automatic Equalize is started if the
battery charge current is greater than 6% of the
battery’s nominal capacity.
EQ Start Cap:
The system is transferred to Equalize
Charge mode when remaining battery capacity
decreases to this setting.
EQ Stop Curr:
When in Equalize Charge mode and
the battery charge current decreases below this
setting for the "EQ Stop Delay" time period, the
system is transferred to Float Charge mode. For
example, a value of 0.010C10 means that when the
charging current is less than 1% of the battery’s
nominal capacity, the system returns to the Float
mode.