Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
96
Note:
You can set High2, High1, and Low temperature alarms
for each temperature sensor (from the Web Interface).
Note that you cannot set high and low temperature
alarms for individual temperature sensors from the Local
Menus. High and low temperature alarm settings for the
temperature sensors set as ambient are found in the
Device Information / Power System / Settings tab. High
and low temperature alarm settings for the probes set as
battery are found in the Device Information / Battery
Group / Settings tab.
Communication
COMMUNICATION MENU
Menu Navigation:
Main Menu / Settings / Communication
Note: For WEB Interface; menu items are found under
Maintenance / Network Configuration.
"Communication" Parameter Settings:
•
DHCP:
The DHCP function allows the Controller to
acquire an IP address automatically. This function can
only be enabled or disabled via the local LCD display and
keypad. If this function is enabled and the acquisition of
an IP address fails, an alarm is generated. If the
acquisition of an IP address is successful, you need to
record the IP address automatically acquired by the
Controller to access the Controller via the Web Interface.
•
IP Address:
Sets the Controller's IP address.
Enter the address in the format nnn.nnn.nnn.nnn, where
0 ≤ nnn ≤ 255.
The address must be a valid address and must not be
255.255.255.255.
•
Subnet Mask:
Sets the Controller's network netmask.
Enter the address in the format nnn.nnn.nnn.nnn, where
0 ≤ nnn ≤ 255.
•
Default Gateway:
Sets the Controller's gateway address.
Enter the address in the format nnn.nnn.nnn.nnn, where
0 ≤ nnn ≤ 255.
This is the address of the gateway of the network on
which the Controller resides.
The address must be a valid address and must not be
255.255.255.255.
Controller
CONTROLLER MENU
Menu Navigation:
Main Menu / Settings / Controller
Note: For WEB Interface; menu items are found under the
Maintenance and Configuration menus.
"Controller" Parameter Settings:
•
Language:
Select the language the menus are displayed
in.
•
Date:
Sets the date.
•
Time:
Sets the time.
•
Keypad Voice:
Sets the keypad sound on or off.
•
Reload Config:
Reloads the configuration that resides in
memory (restores factory defaults).
•
Download Config:
Downloads a configuration package
into the Controller.
•
Auto Config:
Auto configures the Controller for the
devices connected to it.
ECO MODE (ENERGY OPTIMIZATION) MENU
Menu Navigation:
Main Menu / ECO Mode
Note: For WEB Interface; menu items are found under Quick
Settings / ECO Mode Setting.
"ECO Mode" Parameter Settings:
•
ECO Mode:
Enables or disables the Energy Optimization
Mode feature for all rectifiers. When enabled, the
following parameters can be set.
•
Best Oper Point:
Percent of full load capacity that the
rectifiers operate under in the Energy Optimization
mode.
•
Energy Save Pt:
Energy Optimization is disabled if
the load is greater than this setting.
•
Fluct Range:
If load fluctuation is less than this value,
rectifiers are not turned on or off for Energy
Optimization.
•
Cycle Period:
This is the time period that rectifiers
are turned on and off to maintain an equal operating
time for all rectifiers in the system.
•
Rects ON Time:
Time all rectifiers are turned on at
End of Cycle.
•
Turn Off Delay:
When the Energy Optimization
feature determines a rectifier can be switched off,
this is the time delay before the rectifier is switched
off.
Manual Menu
Note:
Menu items shown with an asterisk (*) can be changed while
in Auto Mode. Before any
other
settings in this section can be
changed, you must first place the ACU+ in the Manual mode.
See "’Man/Auto Set Parameter Settings" for a procedure.
Items that can only be changed in the Manual mode will revert
to their previous settings when the Controller is returned to the
Auto mode.