Communication Failure: The Rectifier’s protection indicator (yellow) will flash
should it experience a communication failure. The failure information will be reported
to the Controller and the Controller will process the failure accordingly. During a
communication failure, in order to protect the battery, the Rectifier output voltage will
automatically be adjusted as follows. When used with the SCU+ Controller, Rectifier
output voltage goes to a default value (53.5 V, which can be modified using the
SCU+ Controller). When used with the ACU+ Controller, Rectifier output voltage
goes to the ACU+ float voltage setting (this setting is stored in the Rectifier). The
Rectifier will revert to normal operation once normal communication is restored.
Rectifier Output Current Imbalance:
a) When the average current of all Rectifier Modules is greater than 20% of full
rated current, and the difference between local Rectifier Module current and
average current is greater than 16% of full rated current, the yellow protection
indicator will illuminate.
b) When the average current of all Rectifier Modules is greater than 10% of full
rated current, and local Rectifier Module current is less than 1.5% of full rated
current, then the red fault indicator will illuminate.