Brochures and Data Sheets

User Instructions UM1R483500E
Spec. No. 1R483200 (Model R48-3200) Issue AG, November 20, 2012
Spec. No. 1R483200E (Model R48-3200E)
Spec. No. 1R483500E (Model R48-3500E)
Page 9
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Typical Input Data (1R483200E): 60 Hz input.
a) System output is initially adjusted to 54.48 volts DC as measured at the system
sense points at 50% of full load and nominal input. “Percent of Full Load” refers
to percent of 55 Amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.42
89
11
12.2
--
36.53
25
3.80
798
782
98.0
95.71
114.64
50
7.42
1553
1547
99.6
96.62
178.38
75
11.18
2334
2331
99.8
96.31
293.16
100
15.20
3166
3164
99.9
95.64
471.10
110
16.36
3406
3406
99.9
95.54
518.52
120
16.28
3424
3422
99.9
95.00
583.64
240
0
0.50
121
10
8.80
--
35.67
25
3.33
806
780
96.8
95.90
109.19
50
6.44
1556
1543
99.1
96.84
166.43
75
9.77
2356
2349
99.7
96.63
270.25
100
12.86
3094
3089
99.8
96.19
401.59
110
14.08
3395
3386
99.8
96.05
456.47
120
14.06
3398
3394
99.8
95.35
539.14
b) Maximum Input Current: at 100% of full load with output adjusted to 58 volts
DC as measured at the shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
19.30
Figure 10
Efficiency Curve [R48-3200E (1R483200E)]