Brochures and Data Sheets

2 106DRB-NS722 / 0814
EmersonNetworkPower.com/EnergySystems (North America)
© Emerson Network Power, Energy Systems, North America, Inc. 2014.
Business-Critical Continuity
, Emerson Network Power
, the Emerson Network Power logo, Emerson
and Consider it Solved are service marks and
trademarks of Emerson Electric Co. EnergyMaster
, eSure
, NetPerform
, NetReach
, NetSpan
, NetSure
and NetXtend
are trademarks of Emerson
Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications subject to
change without notice.
Rear View (Covers Removed)
DC Output and AC Input Connections
R48-3500e – eSure
Rectifier
M820D – ACU+ Controller
NetSure
722
Technical Specifications
System Features
System Voltage, Nominal -48 VDC (-42.0 VDC to -58.0 VDC range)
Control Microprocessor ACU+
Rated Output Capacity
Main Shelf (with ACU+) 365 amps at -48 VDC
Expansion Shelf 438 amps at -48 VDC
System 2000 amps
Rectifier 3500 W (R48-3500e)
Physical Characteristics
Mounting Width 23 inches (584 mm)
Mounting Depth 18.8 inches (478 mm)
Height 5.22 inches (133 mm)
Front Projection 6.0 inches (152 mm)
Weight
Main Shelf: 30.0 lb. (13.6 kg)
Expansion Shelf: 28.0 lb. (12.7 kg)
ACU+: 2.2 lb. (1.0 kg)
Rectifier: 7.0 lb. (3.2 kg)
Environmental
Operating Temperature -40 °C to 65 °C (-40 °F to 149 °F) with derating above 45 °C (113 °F)
Storage -40 °C to 85 °C (-40 °F to 185 °F)
Humidity 0% to 95% relative humidity, non-condensing
Altitude
-200 ft. to 10,000 ft. (-61 m to 3048 m), derate 3 °C per 1000 ft.
above 5000 ft.
Ventilation Rectifiers are fan-cooled front to rear
EMI/RFI Suppression
Conforms to FCC rules Part 15, Subpart B, Class B and EN55022 Class B,
radiated and conducted
Safety Compliance
Recognized to UL60950-1; CAN/CSA 22.2 No. 60950-00;
NEBS Level 3 Certified
Ordering Information
Part Number Description
582127100 NetSure
722 DC power system
1M820DNA ACU+ controller
1R483500E 3500 watt eSure
rectifier
588705000 Power shelf