Brochures and Data Sheets
System Application Guide SAG582127100
Spec. No. 582127100 (Model 722NBBB) Issue AA, May 7, 2013
Page 19 of 26
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RS-485
(System External Interface Circuit Card)
LA
(System Internal Interface Circuit Card)
Signal
TB5
Signal
TB5
RS-485 (+)
1
Load Fuse Alarm 1
13
RS-485 (-)
2
Load Fuse Alarm 2
14
OPT
(System Internal Interface Circuit Card)
Load Fuse Alarm 3
15
Load Fuse Alarm 4
16
Signal
TB5
Load Fuse Alarm 5
not available
Battery 2 Shunt (-)
3
Load Fuse Alarm 6
not available
Battery 2 Shunt (+)
4
Load Fuse Alarm 7
not available
Load Shunt (-)
5
Load Fuse Alarm 8
not available
Load Shunt (+)
6
Load Fuse Alarm 9
not available
LVD2 Sense (-)
7
Load Fuse Alarm 10
not available
LVD2 Drive (+)
8
STD
(System Internal Interface Circuit Card)
SPD (-)
not available
LVD2 Drive (-)
9
Signal
TB5
SPD (+)
not available
Battery 1 Shunt (-)
not available
LVD2 Sense (+)
10
LVD1 Drive (+)
not available
BA
(System Internal Interface Circuit Card)
LVD1 Drive (-)
not available
Battery 1 Shunt (+)
not available
Signal
TB5
LVD1 Sense (-)
not available
Battery Fuse Alarm 1
11
LVD1 Sense (+)
not available
Battery Fuse Alarm 2
12
Battery Fuse Alarm 3
not available
Battery Fuse Alarm 4
not available
Table 6
System Interface Circuit Cards Signals Available on TB5