Data Sheet
2 EN609DRA-NS4015 / 0913
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications subject to
change without notice.
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2013.
Business-Critical Continuity
™
, Emerson Network Power
™
, the Emerson Network Power logo, Emerson
™
and Consider it Solved are service marks and
trademarks of Emerson Electric Co. EnergyMaster
™
, eSure
™
, NetPerform
™
, NetReach
™
, NetSpan
™
, NetSure
™
and NetXtend
™
are trademarks of Emerson
Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.
Battery Backup Time (min.)
Number of Strings/Trays
Load 1 2 3 4 5
5 kW 15 50 >60 >60 >60
10 kW 9 18 31 44 50
15 kW 10 18 27 32
20 kW 7 12 18 24
25 kW 5 8 13 18
30 kW 6 10 13
Note: Backup times based on 25 ˚C ambient
with fully charged batteries.
Overview
NetSure
™
4015
Technical Specifications
System Input
Nominal Voltage 380 VAC, 400 VAC, 480 VAC; 3 phase, 4 wire
Input Voltage Range
Operating range: 260 VAC to 530 VAC
Full power: 304 VAC to 530 VAC; Derated: 260 VAC to 304 VAC
Input Frequency 45 Hz to 65 Hz
Upstream Breaker
(recommended)
63 A @ 400 VAC, 50 A @ 480 VAC; 30 kW full power
System Output
Voltage Range 290 VDC to 400 VDC adjustable
Output Power 30 kW maximum @ Vout > 336 VDC
Voltage Regulation 0.5% for full operating range
Grounding Configurations
• High resistance mid-point ground with ground fault detection
• Negative pole ground
Efficiency Peak: 97%
Environmental
Operating Temperature Full rating: -5 °C to +35 °C; Recommend 20 °C to 25 °C with batteries
Relative Humidity 0% to 95% non condensing
Audible Noise < 55 dB(A)
EMI EN 300 386, Class A and FCC Part 15, Class A
RoHS RoHS compliant (pending)
Optional Battery Tray
Battery Type High rate discharge lead acid (VRLA), flame retardant (V0) case
Battery Capacity 35 Watt/cell (15 min. rate), see battery backup table below
Battery Details
28 x 12 V blocks; Enersys DataSafe
®
NPX-35TFR or equivalent
336 VDC nominal, 378 VDC float
Tray Mechanical 4 RU high, 118 kg (260 lbs) installed
Mechanical Cabinet Specification
Rectifier Form Factor Hot pluggable module
Rectifier Weight 10 kg (22 lb.)
Rack Dimensions (H x W x D)
24 RU: 1194 mm x 600 mm x 1000 mm (47" x 24" x 40")
42 RU: 2000 mm x 600 mm x 1000 mm (79" x 24" x 40")
System Weight
See System Application Guide
Cabling Details Top or bottom cabling; front and rear access required
Safety
Safety Agencies UL Listed per UL60950-1 (cUL for Canada)
CE Marking per low voltage directive (EN 60950) and the EMC directive
Cabinet IP 20
Ordering Information
Part Number Description
584000300 NetSure
™
4015, 30kW 400V DC Power System
Email NetSure4000Series@Emerson.com for more information.
1
Load Distribution Sub-Rack (6 RU high)
Up to (9) circuit breakers, output from 6 A-63 A
Optional 125 A main load breaker (req for UL)
Up to (2) sub-racks per system
2
Power and Control Sub-Rack (6 RU high)
2 x 15 kW rectifiers, ACU+ controller
2 x AC input circuit breaker, 3-phase, 4-wire
Local system shutdown
Ground fault detection (HRMG only)
3
Battery Tray (4 RU high)
28 x 35 W/cell – 336 VDC nominal; 378 VDC float
Remote trip c.b.; Up to (5) battery trays/system
1
2
3
3
System Shown in a 24U Rack