Application Guide

SAG584000300 System Application Guide
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System
Spec. No. 584000300 (Model 4015-X003)
Page 8 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
Load Distribution Sub-Rack List 21-24
Rear
HRMG Configuration NPG Configuration
Sub-Rack
Grounding Stud
Sub-Rack
Grounding Stud
DC Distribution Leads Openings
for 25mm (1) Conduit
(snap bushings are furnished
for use without conduit)
Removable
Panel
Rear
Return Bar
Grounding Point
(opening for 19mm [0.75"]
conduit provided)
Front
Front
Conduit Grounding Points
(opposite side also)
(both HRMG and NPG)
Distribution Blocks hold factory wiring
in unused breaker locations for ease
of adding future circuit breakers.
(both HRMG and NPG)
Customer
Load Connections
to DC Distribution
Circuit Breakers
Removable Panel
(for installation)
(both HRMG and NPG)
Customer
Load Connections
to DC Distribution
Circuit Breakers
Customer
Load Return
Connections
to Return Bar
List Row Breaker HRMG NPG
21 X X
22 X X
23 X
24 X
Front
DC Distribution
Circuit Breakers - 9 positions
(4A, 6A, 8A, 10A, 16A, 20A,
25A, 32A, 40A, 50A, 63A)
Future Circuit
Breaker Mounting
Positions
Optional (List 21, 22)
Row DC Distribution
Circuit Breaker (125A)
DC Distribution
Input Leads
(from Power and
Control Sub-Rack)
Front
Mounting
Flanges