Application Guide

System Application Guide SAG584000300
NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013
Spec. No. 584000300 (Model 4015-X003)
Page 3 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
General Specifications
Family: NetSure
System Spec. No.: 584000300
System Model: 4015-X003
System AC Input Voltage Nominal 380/400/480 volts AC, three phase, 50/60 Hz, with an
operating range of 260 to 530 volts. Acceptable input frequency
range is 45 to 65 Hz. A single 4-wire (no neutral) AC input feed
supplies both rectifiers.
System Output Voltage (max.): 400V DC
Output Capacity:
System: 89A, 30kW (maximum)
Rectifier: 44.6A @ 336V DC to 37.5A @ 400V DC, 15kW (maximum)
System Agency Approval: UL Listed per UL60950-1 (cUL for Canada). CE Marking per low
voltage directive (EN60950) and the EMC directive.
(See 1.5.1 Safety Compliance” on page 27.)
EMI: EN 300 386, Class A and FCC Part 15, Class A
Framework Type: Rack Mounting in an IT Rack (EIA-310-D Compliant)
Mounting Width: 19 Inches (483mm), nominal
Mounting Depth:
Power and Control Sub-Rack: 724mm (28.5 inches)
Load Distribution Sub-Rack: 257mm (10 inches), HRMG Configuration
317mm (12.5 inches), NPG Configuration
Battery Tray: 838mm (33 inches)
24U Rack Dimensions: 1194mmH x 600mmW x 1000mmD (47"H x 24"W x 40"D)
42U Rack Dimensions: 2000mmH x 600mmW x 1000mmD (79"H x 24"W x 40"D)
Access: Front and rear for installation and maintenance.
Front for operation.
Control: Microprocessor
Color: Black
Environment: -5°C to +45°C (+23°F to +113°F).
Full Rating: -5°C to +35°C (+23°F to +95°F).
Note: Battery manufacturers recommend an operating temperature
of 25°C (77°F). Ambient temperatures higher than this reduce
battery life; temperatures lower than this reduce battery capacity.
For optimal battery performance and service life, battery temperature
should be maintained between +20°C to +25°C (+68°F to +77°F).
See detailed specifications on page 26.
Customer Supplied IT Rack Guidelines
If you plan to assemble / configure your own system, note that the NetSure 4000 Series components
(power and control sub-rack / load distribution sub-rack / battery tray) were evaluated as a UL Listed
system in an Emerson Network Power DCM IT Rack in an ambient of +35°C (95°F), with a front and rear
door free area ratio of 83%.