Application Guide

SAG584000300 System Application Guide
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System
Spec. No. 584000300 (Model 4015-X003)
Page 22 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
Return Busbar (-Bus) Grounding (NPG Configurations Only)
The return busbar (Bus) in a negative pole ground (NPG) configuration is to be connected to ground. A
grounding connection point for the return busbar (-Bus) is provided on the negative bus in the power and
control sub-rack. This connection can also be made on the rear of the load distribution sub-rack, if furnished.
Note: When the system is pre-assembled and pre-wired in a factory furnished IT rack (List R1, R2), a
grounding lead is factory connected between the Bus in the power and control sub-rack and the rack
ground bar located on the rear left side of the furnished IT rack.
Refer to Table 6 for recommended grounding wire size and lug selection. For convenience, a grounding
cable is furnished loose as shown in Table 6.
Return Busbar (-Bus) Grounding
Recommended
Wire Size
Lug Requirements
Recommended Lug
(Emerson P/N)
Furnished Grounding Cable
4 AWG
(25mm
2
)
To Power and
Control Sub-Rack:
2-Hole,
1/4” Bolt Clearance
Holes, 5/8" Centers
245346800
P/N 555262, 965mm (38”),
terminated on both ends with
lug P/N 245346800.
To Load Distribution
Sub-Rack: None
(screw-clamp type
terminal provided)
--
--
Table 6
Recommended Return Busbar (-Bus) Grounding Wire Size and Lug (NPG Configurations Only)