Ordering Guides

3
095ORB-GMCSS / 0614
Compact Indoor and Outdoor Cell Site Solutions
Outdoor Solution Without DC Power
The outdoor site solution (without DC power) is a small single
sided low-cost outdoor rated aluminum enclosure with a heat
exchanger cooling system, equipment rack and fused
terminal blocks.
n NEMA 3R design protects equipment from water and dust,
while maintaining a cool operating environment
n UL and cUL listing ensures documented performance
n GR-487-CORE Issue 3 design ensures system reliability
and durability
n Aluminum construction provides superior protection for
panels, cables and splices, offering a long, corrosion resistant,
problem-free service life
NetXtend
Compact enclosures are ideal for inconspicuous
deployment of Alternative Access Vendor (AAV) applications,
mobile 2G/3G/4G cellular base stations, DAS nodes, mobile
backhaul, remote power solutions, fiber (FTTx) nodes, advanced
metering management (AMM) nodes or hybrid controller
systems (solar, wind, etc.).
Ordering Information
Emerson
Part Number
Description
F2014020 NetXtend
Compact – Base Cabinet
equipped with:
(1) NetXtend
Compact 2416 cabinet with heat exchanger
(1) 19" equipment rack system (13 RU)
(2) Fuse modular terminal blocks
F2014015 NetXtend
Compact – Base Cabinet with Wall Mount Kit
equipped with:
(1) NetXtend
Compact 2416 cabinet with heat exchanger
(1) 19" equipment rack system (13 RU)
(2) Fuse modular terminal blocks
(1) Wall mount kit
F2014016 NetXtend
Compact – Base Cabinet with Pole Mount Kit
equipped with:
(1) NetXtend
Compact 2416 cabinet with heat exchanger
(1) 19" equipment rack system (13 RU)
(2) Fuse modular terminal blocks
(1) Pole mount kit
Accessories
F1010408 (1) Wall mount kit
F1010409 (1) Pole mount kit
Technical Specifications
Physical Characteristics
Framework Type
NetXtend
Compact Enclosure
Available Space
Up to 13 RU, 19" W
Dimensions
Enclosure: 24" H x 24" W x 16" D
Mounting
Wall/H-frame or pole mount
Weight
64 lb.
Access
Front
Environmental
Climate System 500 W heat exchanger
Operating Temp. -40 °C to +52 °C
Storage Temp. -40 °C to +75 °C
Relative Humidity 100%
EMI/RFI Conforms to FCC rules Part 15, Subpart B, Class B and
EN55022 Class B, radiated and conducted
Safety Compliance UL Listed, cUL, GR-487
Diagrams
Wall Mounting
27 fo 14 egaPnoitamrofnI yrateirporPtnempiuqE tnalP edistuO
1. Aligning each hole of the wall-mount brackets to the holes
of the enclosure, 4 places.
2. Securing wall-mount brackets to the enclosure, 8 places.
3. Attaching wall-mount brackets to wall, 4 places.
Detail A
Fig. 30 : Installing NetXtend™ Compact Enclosure to Wall
Pole Mounting
Emerson Network Power
Outdoor Enclosures
631-205-411
Version C, July 29, 2013
27 fo 93 egaPnoitamrofnI yrateirporPtnempiuqE tnalP edistuO