Ordering Guides
For additional information or questions visit or call:
Web: www.EmersonEnergy.com n Tel: 1-800-800-1280 (USA and Canada)
5
095ORA-NS211 / 0315
NetSure 211 – 23" Shelf, 2 RU NetSure 211 – 19" Shelf, 2 RU
Netsure 211 Ordering Guide
-48 VDC Power Solutions – Mini System
Configuration 2. NetSure
™
211 – 2 RU, Up to 100 A (N+1)
Catalog Number Part Number Quantity Description Shelf Size
Step 2a: Choose Rectifier Shelf (includes ACU+ controller and space for distribution)
58213660005 NetSure 211 power system shelf 19" x 2 RU
58213660006 NetSure 211 power system shelf 23" x 2 RU
Step 2b: Select Distribution, 1 required per rectifier shelf
582136600NA (2) Load breaker positions, (2) battery breaker positions and (5) GMT fuse positions (10 A max), no LVD
582136600BA (2) Load breaker positions, (2) battery breaker positions and (5) GMT fuse positions (10 A max), battery LVD
582136600NC (4) Load breaker positions and (5) GMT fuse positions (10 A max), no LVD
582136600BC (4) Load breaker positions and (5) GMT fuse positions (10 A max), battery LVD
582136600LC (4) Load breaker positions and (5) GMT fuse positions (10 A max), load LVD
582136600NF (5) 10 A GMT fuse positions and (8) 15 A GMT fuse positions, no LVD
582136600BF (5) 10 A GMT fuse positions and (8) 15 A GMT fuse positions, battery LVD
Step 2c: Select GMT Fuse Module if Required
545332 (6) position GMT fuse position option board, takes up (2) load breaker positions
Note: Up to (1) for Lists NA and BA. Up to (2) for Lists NC, BC, LC. Cannot be used in Lists NF and BF.
Step 2d: Select Line Cord, 2 required per shelf
545478* 14' AC cord, 120 VAC, 5-15P fits wall outlet
545252 14' AC cord, 120 VAC twist-lock L5-30P
540946 14' AC cord, 208/240 VAC twist-lock L6-30P
* This cord is for use with 1R48500 rectifiers and the 19" shelf only.
Step 2e: Select up to 2 Temperature Probes if Required (one battery and one ambient or two battery)
58213660090 3 meter temperature probe
58213660091 10 meter temperature probe
Step 2f: Select GMT Lead Assemblies if Using GMT Fuses in Distribution (not required for 545332)
58213660060 GMT lead assembly for (5) 10 A GMT fuses
58213660061 GMT lead assembly for (8) 10 A GMT fuses for lists NF and BF
58213660062 GMT lead assembly for (5) 15 A GMT fuses for lists NF and BF
Step 2g: Select Rectifier Quantity (Up to 4 rectifiers per 19" shelf or Up to 6 rectifiers per 23" shelf)
1R48500 500 watt (10 amp) rectifier
1R481000 1000 watt (20 amp) rectifier
Note: 1000 watt rectifier de-rates to 500 watts with 120 volt AC input.