Brochures and Data Sheets
7
Additional Information
For additional specification, engineering and installation information, request specification number 582136600 (system),
1R48500 or 1R481000 (rectifiers), or 541434 (battery cabinet).
For ordering information on the complete system, request SAG582136600.
Emerson Network Power—
a complete spectrum of best-in-class
reliable power, precision environmental
and connectivity solutions for
today’s telecommunications and
data network infrastructure
Rectifier Specifications, R48-500 and R48-1000
AC Input
Nominal Voltage 120, 208, 240VAC
Operating Voltage Range 85 to 300VAC
Frequency 45 Hz to 65 Hz
Power Factor (PF) >0.90 for 25%-50% load, >0.98 for 50%-100% load and >0.99 for 100% load
at 208Vac, 220Vac, 230Vac, 240Vac and 25°C
Total Harmonic Distortion <5% from 50 to 100% of rated load at 208 Voc – 240 Voc
Input Current Max 6.5A both 500W and 1000W
Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value
Operating Efficiency 91% (500W) 92% (1000W)
DC Output
Output Voltage Range -42 to -58VDC
Output Power Constant power limiting operation 500W and 1000W @ -48VDC
(for 1000W, see derating chart for voltages less than 176VDC or temperatures higher than 45°C)
Output Current 10.42A @ -48VDC (500W) 20.83A @ -48VDC (1000W)
Regulation Steady state output voltage remains within +/-1% for any combination of input voltage and temperature
from 5% to 100% load
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 32dBrnC output noise from 0% to 100% load
Wide Band Noise Does not exceed 250mv peak-to-peak, or 100mv rms per Telcordia GR-947-CORE
Psophometric Noise <1mV at 0 to 100% of rated load; <32dBrnc at 0 to 100% of rated load (output voltage > -42V)
Protection High Voltage Shutdown fixed and selective capability. Fixed – requires manual restart.
Selective – If rectifier detects over voltage it will turn off. After 5 seconds it will restart;
if it encounters an over voltage within 5 minutes it will turn off and remain off until reset.
Environmental
Temperature -40 to +75°C, -40 to 167°F
Altitude 2000m, 6560 ft at full power
Ventilation Front to back with speed-controlled fan (field replaceable)
Audible Noise The rectifier does not produce sound levels above 53dB(A), measured 0.6m in front of the rectifier, at the same hori-
zontal line as the middle of the rectifier at 25°C
Status /Alarm Indicators and Monitoring
Visual Indicators
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
Status Settings The SCU controller establishes all rectifier settings
Rectifier Physical Specifications
Mounting Plugin installation
Dimensions (H x W x D) 1.6" x 3.4" x 9.5" (40.8 x 86.5 x 241 mm)
Weight 2.76lbs (1.25kg)
Safety Compliance UL 60950 Recognized (US & Canada)