Ordering Guides
SAG582136600 System Application Guide
Issue AU, February 21, 2014 Spec. No. 582136600 (Model 211
NGFB)
Page 88 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
SPECIFICATIONS
Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000)
supplied with your Power System.
For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B)
supplied with your Power System.
For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (C-
drawing) supplied with your Power System.
1. SYSTEM
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range (Specification Compliant):
(A) -40°C (-40°F) to +65°C (+149°F) with derating output.
(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 90%, non-condensing.
1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product must be located in a Controlled Environment with access to Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut,
or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the
relay rack and 2' for the rear of the relay rack.
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4”
multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf).
Mounting angles are positioned for a 5-inch front projection mounting only.
Flush mounting is done using optional kits.
1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be
blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient
Temperature Range stated above.
1.2 Compliance Information
1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6.
Note: This level of protection is a widely used standard for telecommunications power
equipment. As with all such equipment, it is the end user's responsibility to provide an
adequately sized Surge Suppression Device at the commercial power service entrance of
the building that reduces all incoming surges to levels below the classes/categories
stated for the equipment.
1.2.2 Safety Compliance:
(A) This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data
Processing, or Information Processing Equipment.
(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and
Certified by UL ("c UR") as a Component Type Power Supply.