Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown)
and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)
List NF Distribution
Unit shown. List BF,
LF, BC, LC, and NC similar.
Front
Battery, Battery Return,
and CO Ground Leads
Enter Here
Distribution
Unit
List 65 provides 3' long, 2 AWG, battery cables
terminated on one end with lugs to connect to
the input battery landings and on the other end
with an Anderson connector.
List 66 provides 12' long, 2 AWG, battery cables
terminated on one end in an Anderson connector
and left unterminated at the remaining end for
connection of battery lugs.
Battery: 1/4-20 studs (w/hardware)
on 5/8" centers for installation
of customer provided two hole lugs.
CO Ground: 10-32 studs (w/hardware)
on 5/8" centers for installation
of customer provided two hole lugs.
OBSERVE PROPER
POLARITY WHEN
MAKING BATTERY
CONNECTIONS
Right Side
-48 Battery Leads
Battery Return Leads
CO Ground Lead
CO Ground Lead
List BF, LF, and NF
Distribution Unit
List BC, LC, and NC
Distribution Unit
-48 Battery Leads
Battery Return Leads
Right Side