Ordering Guides
SAG582136600 System Application Guide
Issue AU, February 21, 2014 Spec. No. 582136600 (Model 211
NGFB)
Page 78 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
Yellow Jumper/Alarm
Lead (P/O Cabinet)
Orange Wire on
541434 not used
Procedure
1. Remove quick connect terminal from YELLOW
battery cabinet alarm lead.
2. Wire per table below.
1st BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Cabinets
alarm
wire
2nd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
3rd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Connect to
shelf per
table below.
alarm
wire
alarm
wire
External Battery Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is ac
tivated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
NO
CONNECT YELLOW WIRE TO:
Alarm Cable
on shelf
YES
NO
YES
545495
541311
Shelf List
1 or 2
5 or 6
BREAKER ALARM CONNECTION