Ordering Guides
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211
NGFB) Issue AU, February 21, 2014
Page 77 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home Home
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately
and supplied loose.
Must be wired
by the customer to
each circuit breaker
“C (Common)”
alarm terminal)
see
previous
page
Procedure
1. Connect kit-supplied YELLOW jumper/alarm lead
(P/N 524384) to circuit breaker “C (Common)”
alarm terminals on ALL Battery Disconnect Circuit
Breakers. Connect remaining per table below.
2. There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
1st BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Disconnect Circuit
Breakers when (1) to (3) Battery Trays are Used
(Side cover removed in illustration
to show wiring d
etails.)
see
previous
page
see
previous
page
3. On ALL Battery Disconnect circuit
breakers, there should be a factory
connected Jumper connected from
the bottom terminal on the circuit
breaker to the circuit breaker “NC
(Normally Closed)” alarm terminal.
2nd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
3rd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)
Connect to
shelf per
table below.
*
No terminal
on 524384
jumper
External Battery
Disconnect Circuit Breaker Alarm Input:
A battery disconnect circuit breaker alarm is activated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.
Must order Cable 545495
R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
O-R Lead of 541311. Splice and heat shrink tubing included with 541311
NO
CONNECT YELLOW WIRE TO:
Alarm Cable
on shelf
YES
NO
YES
545495
541311
Shelf List
1 or 2
5 or 6