Ordering Guides
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211
NGFB) Issue AU, February 21, 2014
Page 69 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 6.
2) For other available lugs, refer to drawings 031110100 through 031110300.
Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width, 0.61 inches.
Ordering Notes
1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.
When making connections, observe correct polarity.
2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables.