Ordering Guides
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211
NGFB) Issue AU, February 21, 2014
Page 65 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
factory connected to these terminals. The other half (includes mating connector on one end and
un-terminated on the other end) is ordered separately.
If an additional -48V Digital Input cable is ordered, one half of the cable is factory connected in the shelf.
The other half includes mating connector on one end and is un-terminated on the other end. The
additional -48V digital input cable must be ordered separately.
Restrictions
Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Load Distribution Wiring (GMT Fuses) (Lists BG and NG only)
Features
♦ Load and load return leads are connected to a screw-type terminal block located on the front of the
Distribution Unit.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 20 to 12 AWG.
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of
fuse amperage sizes, and that two different types of receptacles are provided.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco
350537-3 [reel].