Wiring Notes
Refer also to the next section, Wiring Illustrations.
Shelf Frame Grounding Stud
Features
An M5 frame grounding stud with hardware is provided on the rear of the shelf.
Restrictions
Recommended frame ground wire size is 6 AWG.
AC Input Branch Circuit Protection and Wiring
Features
Each shelf contains one (1) or two (2) side mounted plug-in AC input connector(s).
AC Input Cable Assemblies/Line Cords are available that plug into the shelf’s AC input connector.
Restrictions
Lists 1 and 2 require one (1) AC input branch circuit.
The AC input branch circuit feeds two (2) (List 1) or three (3) (List 2) rectifiers.
Refer to the following table for recommended branch circuit protection.
Lists 5 and 6 require two (2) AC input branch circuits.
Each AC input branch circuit feeds two (2) (List 5) or three (3) (List 6) rectifiers.
Refer to the following table for recommended branch circuit protection.
AC Input Branch Circuit Protection*
System
208/240VAC Input 120VAC Input
500W Rect. 1000W Rect. 500W Rect. 1000W Rect.
58213660001
58213660005
(2-Rectifiers per AC Feed)
15A 15A 15A 20A
58213660002
58213660006
(3-Rectifiers per AC Feed)
15A 20A 20A 25A / 30A
* Protective devices should be of the time-delay or high inrush type.
For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input
branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this
document.
External Alarm and Monitoring Wiring
Features
List 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on
the Customer Interface Board mounted inside the shelf. One half of a Relay Outputs Cable is factory
connected to these terminals. The other half (includes mating connector on one end and un-terminated
on the other end) is ordered separately. If ordered, one half of a Digital Input Cable is factory connected
to these terminals. The other half includes a mating connector on one end and is un-terminated on the
other end.
List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the
SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is