NetSure™ 211BC Battery Cabinet (Spec. No. 545506)
Features
♦ The NetSure™ 211BC Battery Cabinet is rated at 30
amperes, and can be mounted in a 23” nominal relay
rack, or mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie
into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the
table under Ordering Notes) into the Battery Cabinet
provided.
♦ Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet
into another.
Ordering Notes
1) Order by Spec. No. 545506 as required.
2) Also order four (4) batteries per Battery Cabinet per
the following table.
Battery
Manufacturer
Manufacturer
P/N
Emerson P/N Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
Enersys
SBS B10
140553
38
28.20
Enersys
SBS 40
140581
38
28.00
C&D/ Dynasty
TEL12-30
140455
30.5
26.70
C&D/ Dynasty
TEL12-45
140454
46
26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.
Att
ach Frame G
round Land
ing
Point A
dapter to C
abinet
F
ra
me
G
ro
u
nd
in
g
Po
in
t
(1/4-20
St
ud
s
on
5/
8
” C
e
nters)
Frame Gro
und
Lan
din
g
P
oint Adapte
r P/
N 556
87
2