NetSure™ 211BC Battery Cabinet (Spec. No. 545534)
Features
The NetSure™ 211BC Battery Cabinet is rated at 30
amperes, and can be mounted in a 19” or 23” nominal
relay rack, or mounted to a suitable wall.
The Battery Cabinet contains one (1) 40 ampere battery
disconnect circuit breaker.
Battery circuit breaker alarm leads are provided to tie into
the power system’s alarm circuit.
The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
Cables to connect the batteries (as specified in the table
under Ordering Notes) into the Battery Cabinet provided.
Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into
another.
Ordering Notes
1) Order by Spec. No. 545534 as required.
2) Also order four (4) batteries per Battery Cabinet per the
following table.
Battery
Manufacturer
Manufacturer
P/N
Emerson P/N Capacity Amp-Hours
(8Hr rate)
Weight (lb)
per Battery
Enersys SBS B10 140553 38 28.20
C&D / Dynasty TEL12-30 140455 30.5 26.70
3) When wall mounted, also order a battery cabinet frame grounding landing point adapter P/N 556872.
This adapter installs in the relay rack mounting bracket holes located on either side of the cabinet.