Ordering Guides

SAG582136600 System Application Guide
Issue AU, February 21, 2014 Spec. No. 582136600 (Model 211
NGFB)
Page 40 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
Features
1U-high GMT fuse panel that provides Single Load
Distribution (-48V)
Provides twenty (20) 0A to 15A GMT fuse load
distribution positions.
Caution: At +40°C and +65°C ambient, a fuse with a
rating of greater than 10 amperes SHALL
HAVE an empty mounting position between
it and any other fuse.
Maximum Capacity: 80A @ +40°C and 80A @ +65°C
Factory mounted and connected to List 5 or 6 shelf.
If the Distribution Unit in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG
loads are disconnected.
If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive
battery is provided to an alarm terminal. Alarm circuit is factory connected to activate the Power System
Controller fuse alarm
Restrictions
For use with List 5 and 6 only.
Mounts only immediately above List 5 or 6 shelf.
Maximum distribution current is 80A.
See also the Restrictions under “GMT Load Distribution Fuses in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required.
Also order the following as required.
2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.