Ordering Guides

System Application Guide SAG582136600
Spec. No. 582136600 (Model 211
NGFB) Issue AU, February 21, 2014
Page 39 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
List NG: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, battery cables, and ten
(10) GMT fuse load distribution positions (15A
maximum).
Two (2) 8 AWG 48” long battery cables are factory
connected inside the shelf. These cables are
terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson
battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1.
Contacts (two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A
fuses.
See also the Restrictions under “GMT Load Distribution Fuses in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71, 72 or 73.
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.