Ordering Guides

System Application Guide SAG582136600
Spec. No. 582136600 (Model 211
NGFB) Issue AU, February 21, 2014
Page 37 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
List NA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and w/out Low Voltage Disconnect
Features
Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, two (2) bullet nose-type
circuit breaker load distribution positions, two (2) bullet
nose-type circuit breaker battery disconnect positions,
five (5) GMT fuse load distribution positions.
Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is
required between GMT fuses greater than 5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.