List BA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, two (2) bullet
nose-type circuit breaker load distribution positions, two
(2) bullet nose-type circuit breaker battery disconnect
positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a
21A @ +65°C (+149°F) maximum capacity. Maximum
GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than 5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
5) The controller remains powered when the LVBD contactor opens. Specify if you require List BA to be
factory configured for the controller not to be powered when the LVBD contactor opens.