Ordering Guides

SAG582136600 System Application Guide
Issue AU, February 21, 2014 Spec. No. 582136600 (Model 211
NGFB)
Page 30 of 105
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
List LF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Load Disconnect (LVLD)
Features
Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery
connection points, and thirteen (13) GMT fuse load
distribution positions.
Five (5) 0A to 15A GMT fuse load distribution
positions.
Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated
100A at +40°C (+104°F) and 59.5A at 65°C (+149°F).
Unless otherwise specified fuses are mounted from bottom to top, starting with the highest capacity and
working to the lowest capacity.
In an ambient of 40°C (+104°F):
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is not required between fuses of
any value.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is not required between fuses
of any value. However, 15A fuses cannot be placed in adjacent fuseholders. 15A fuses must be
separated by a smaller fuse or a space.
In an ambient of 65°C (+149°F):
Fuseholders F1-F8 are rated for a 10A fuse maximum. An empty space is required between 10A fuses.
A fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
Fuseholders F9-F13 are rated for a 15A fuse maximum. An empty space is required between 15A fuses.
10A fuses cannot be placed in adjacent fuseholders. A fuse greater than 3A cannot be placed in a
fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.