User`s guide

Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 86
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.18. Tables [21-24]: TEC2000 Status Inputs
Words [4 63] PLC access: Read / Write
The purpose of these tables is to afford the end user all critical status information from TEC2000
systems. TEC2000 systems are backwards compatible with the 320A/B systems. However, there
are more “things that can be checked” in the TEC2000. For instance, in the TEC2000, the Unit Alarm
is also tripped by a “Valve Drift” Alarm. The “Valve Drift” alarm is not available in the 320A/B systems.
Therefore: For maximum compatibility with the TEC2000 systems, it is recommended that you
enable monitoring the TEC2000 Status Inputs (tables [21-24]). This way, you can ensure you
have all critical status information for any TEC2000 system on the network.
This data is derived from holding registers [1000 - 1003] in the TEC2000 actuator. These table
entries are only filled in if
The particular valve is a TEC2000 system.
The 1746-C is configured to poll these additional registers.
This data is retrieved with a separate Modbus read command when the particular actuator is being
polled (scanned).
These tables are not polled for unless the 1746-C is configured to allow it …
if Table [0] – Word [17] == 0: The TEC2000 status input information is NOT requested when
actuators are polled (
the default).
if Table [0] – Word [17] =/= 0: The TEC2000 status input information is requested when
actuators are polled.
The PLC may reset these tables with any value is prefers. All it needs to do is insert the new value in
the table and send it to the 1746-C as a write command. The table will be reset even though nothing
will be sent out to any actuator.
A read back of Tables [21 - 24] will
If a write command issued: reflect the table write command accepted by the 1746-C
If a read command issued: reflect the last known values of the status input registers in the
TED2000 actuators.