User`s guide
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 62
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.7. Table [8]: Analog Output #1
Words [4 63] PLC access: Read / Write
This table/command tells the actuator to place an appropriate 4-20 mA signal on its analog output
channel. This data is derived from holding register [10] in the actuators and is retrieved with the
“standard data request” - Modbus read command when the particular actuator is being polled
(scanned).
When the 1746-C sends a new value to the actuators, it uses the Modbus function 6 command to write
to holding register [10] in the actuators.
The output is a linear scaling based on:
• 0 (0x0000) = 4 mA
• 4095 (0x0FFF) = 20 mA
Note: Only values 0
4095 are allowed … all others are ignored.
A read back of Table [8] will
• If a write command issued: reflect the write command accepted by the 1746-C
• If a read command issued: reflect the current value of the analog output register in the
actuators.
Note: Please read the Operators Manual the particular actuator for more information.
Note: This is an option that must be installed on the actuator.