Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.4. Table [4]: Valve Position Indication … 0 – 100.0%
Words [4
63] PLC access: Read Only.
The Network Master receives the valve position from the actuator as an integer representing 0
100%
open in 0.1% increments. In other words, it receives a value from 0 – 1000 and each increment
indicates a 0.1%
• 0 Full Closed ( 0.0% open)
• 1000 Full Open (100.0 % open)
This data is derived from holding register [13] in the actuator. It is retrieved with the “standard data
request” - Modbus read command when the particular actuator is being polled (scanned).
Example Table [4] Feedback (48-node network) …
Characteristics:
• Units [1, 3, 4] indicated position is 0% open … probably not operating.
• Unit [2] indicated position is 70.6% open
• The rest of the network’s indicated position is fully open at 100.0% open
Last Node
on 48 Node
Network
First Node
on Network