Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.2. Table [2]: Actuator Operational Status
Words [4
63] PLC access: Read Only.
This data is primarily derived from holding register [6] in the actuator. It is retrieved with the “standard
data request” - Modbus read command when the particular actuator is being polled (scanned).
However, bit-14 is adjusted by the 1746-C.
This status word can be “bit parsed” to give:
Bit-0: LSO is tripped (valve is at the end of its OPEN travel limits)
Bit-1: LSC is tripped (valve is at the end of its CLOSE travel limits)
Bit-2: Valve is moving in the OPENING direction
Bit-3: Valve is moving in the CLOSING direction
Bit-4: Selector Switch is in the Local position
Bit-5: Selector Switch is in the Remote position
Bit-6: Open Torque ALARM is active.
Bit-7: Close Torque ALARM is active.
Bit-8: Valve Stall Alarm is active (valve not moving on command)
Bit-9: Power Monitor Alarm is active (loss of control voltage alarm)
Bit-10: Motor Overload Alarm is active
Bit-11: Phase Monitor Alarm is active (only if Phase Sentry is Installed)
Bit-12: Local (Hardwired) Alarm is active.
Bit-13: Fail Alarm Self-diagnostics Alarm is active.
Bit-14: Comm Alarm … Valve not communicating with the network
(Same as the value “3” in Table [1])
Bit-15: Unit Alarm … Set when any actuator alarm is set.
Note: Bit-0 is the LSB in the word. Bit-15 is the MSB in the word.
Some of these bit indications are repeats of those in table [12]. However, not all.