3.1. Field Connections at the Actuator
Communication connections and wiring are important for the network and the master.
(
The following information was primarily derived from the Controlinc Quick Startup Guide)
3.1.1. Step 1. Plan the Network Topology
Before connecting actuators, the entire network layout should be planned. Topologies may be bus,
redundant bus, E>Net, redundant E>Net, E>Net ring, and redundant E>Net rings. Planning should
include node addressing, wire routing, terminations, and grounding.
3.1.2. Step 2. Select Network Cable
Ensure correct cable is being used.
Networks require twisted pair and shielded cable with characteristic impedance between 50 and
120 Ohms.
Capacitance between conductors must be less that 30 pF/Ft (98 pF/M); 10-15pF/Ft is ideal.
Shielding maybe aluminum foil with drain wire.
If cable has multiple pairs, then individual pair shielding is required.
Only cables with stranded conductors are recommended.
Insulating and outer jacket materials must be selected for the application environment.
The following are acceptable Belden or equivalent cables for most network applications.
AWG 20 18 16 14
Beldon # 8762 8760 8719 8720
Rating 12.8 Pf/fT 12.8 Pf/fT 12.8 Pf/fT 12.8 Pf/fT