A typical E>Net network connection format is in a ring …
• It starts from Port 1 (PRT1) (the top DB9 connector) on the 1746-C as RS232 and connects to
the NIU at the port labeled “Host A”.
• It exits the NIU at the port labeled “Port A” as an RS485 circuit and proceeds to the first valve
actuator, normally addressed as #1, in port A.
• It exits the actuator from Port B and proceeds to the port A next actuator (address #2) and on
until the last actuator on the network is connected.
• The RS485 network then exits port B on the last actuator returns to the NIU at the port labeled
“Port B”.
• The network connection is then transformed back to an RS232 format and exits the NIU via the
port labeled “Host B”
• It connects to the 1746-C via port2 (PRT2) (the bottom DB9 connector).