Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
PRT1 & PRT2 (Green) LED App Note: Green LED Lights & System Initialization with Table [0]
After startup, if table [0] is not initialized shortly after the 1746-C finishes its initial diagnostic
scan, the program starts running with factory default settings. This means that unless the
network actually has 60 actuators on it, the 1746-C will believe the “other valves” are just off
line.
Plus, an operator can often determine when the PLC-RLL actually writes to table [0] (configures
the system) by watching the green LED lights.
For instance …
• On a network that actually has 25 valves on it (addressed 1-25), until table [0] – word [4]
gets initialized with 25, the program thinks that there are still supposed to be 60
actuators on the network … only the last 35 happen to be “off line”.
• Then (if viewing the green LED lights) when a scan starts (LED1 changes state), you will
see the green LEDs “flash” while the 1746-C communicates with valves 1-25.
Then you will observe a “dead space” in time when the program is trying to determine if
any of the final 35 valves “it believes to be connected” are available (
and of course none
are because the network only has 25 valves on it
).
• As soon as a new scan starts (all “60” valves have been checked and ready to scan the
network again … LED1 changes state) then the green LEDs will start flickering again
while the 1746-C communicates with valves 1-25.
Then the “dead space” time will be observed again.
This sequence will repeat until the PLC program initializes the 1746-C by writing to table
[0].