Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.6.2. Upload the 1746-C Firmware
Please refer to the Allen-Bradley SLC-500 BASIC User's Manual (1746-BAS & 1746-BAS-T)
Publication No. 1746-UM004A-US-P 2000
1. Make sure that the terminal program is running and that it is set for 1200 Baud, 8,N,1 and
Software Flow Control (XON/XOFF).
2. Power the PLC rack up.
3. While in the terminal program, the startup screen for the 1746-C will be transmitted on power up.
This also occurs on module reset as well.
4. Press <ENTER> several times to make sure that there is correct communication.
(
The “>”, a line item caret, will appear every time you press it.)
5. Type in the command “CALL 100”.
(
The module then waits for an upload from the terminal program.)
------- ---------
6. Use the “Send Text File” command in your particular terminal program to send the file.
The appropriate file is in “Intel hex format” (
which is an ASCII text file) … all other formats will
create an error.
------- ---------
7. After the file is finished being transmitted, the “>” will appear on the terminal screen to indicate
finished.
8. Type “PROG2” and press <ENTER>.
The module will respond back with a successful dialog. If it doesn’t, repeat the previous step.
If you want (and can) communicate at a 9600 baud rather than 1200 baud, perform
the following NOW:
1. Type in the command : PUSH 9600
2. Type in the command: CALL 78
3. Change your terminal program over to 9600 baud.
4. Continue with the standard procedure.