User`s guide

Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 112
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.4.8. TEC2000 Memory Map … Table for Holding Registers
Description
Reg[1000] ... Discrete Inputs 1000 – 1015
Reg[1001] ... Discrete Inputs 1016 – 1031
Reg[1002] ... Discrete Inputs 1032 – 1047
Reg[1003] ... Discrete Inputs 1048 – 1063
Reg[1004] ... Coils 1000-1015
Reg[1005] ... Coils 1016-1031
Reg[1006] ... Coils 1032-1047
Reg[1007] ... Coils 1048-1063
Reg[1008] ... Coils 1064-1079
Reg[1009] ... Coils 1080-1095
Reg[1010] ... Coils 1096-1111
GENERAL DESCRIPTION HIGH BYTE LOW BYTE
Reg[1011] – Factory Setup Model ID - Char 1 Model ID - Char 0
Reg[1012] – Factory Setup Model ID - Char 3 Model ID - Char 3
Reg[1013] – Factory Setup Model ID - Char 5 Model ID - Char 4
Reg[1014] – Factory Setup Serial Num - Char 0 Model ID - Char 6
Reg[1015] – Factory Setup Serial Num - Char 2 Serial Num – Char 1
Reg[1016] – Factory Setup Serial Num - Char 4 Serial Num – Char 3
Reg[1017] – Factory Setup Serial Num - Char 6 Serial Num – Char 5
Reg[1018] – Factory Setup Serial Num - Char 8 Serial Num – Char 7
Reg[1019] – Factory Setup MFG Date - Char 0 Serial Num – Char 9
Reg[1020] – Factory Setup MFG Date - Char 2 MFG Date - Char 1
Reg[1021] – Factory Setup Motor ID - Char 0 MFG Date - Char 3
Reg[1022] – Factory Setup Motor ID - Char 2 Motor ID - Char 1
Reg[1023] – Factory Setup Motor ID - Char 4 Motor ID - Char 3
Reg[1024] – Factory Setup Motor ID - Char 6 Motor ID - Char 5
Reg[1025] – Factory Setup Motor ID - Char 8 Motor ID - Char 7
Reg[1026] – Factory Setup Motor HP - Char 0 Motor ID - Char 9
Reg[1027] – Factory Setup Motor HP - Char 2 Motor HP - Char 1
Reg[1028] – Factory Setup Motor HP - Char 4 Motor HP - Char 3
Reg[1029] – Factory Setup Motor RPM - Char 1 Motor RPM - Char 0
Reg[1030] – Factory Setup Motor RPM - Char 3 Motor RPM - Char 2
Reg[1031] – Factory Setup Motor Run AMPS - Char 1 Motor Run AMPS - Char 0
Reg[1032] – Factory Setup Motor Run AMPS - Char 3 Motor Run AMPS - Char 2
Reg[1033] – Factory Setup Motor Stall AMPS - Char 1 Motor Stall AMPS - Char 0
Reg[1034] – Factory Setup Motor Stall AMPS - Char 3 Motor Stall AMPS - Char 2
Reg[1035] – Factory Setup Max Torque (0 – 100%) Motor Voltage
Reg[1036] – Factory Setup Torque Spring Type CAM Card Type (Network)
Reg[1037] – User (Field) Setup RO2 Function RO1 Function
Reg[1038] – User (Field) Setup RO4 Function RO3 Function
Reg[1039] – User (Field) Setup RO9 Function RO5 Function
Reg[1040] – User (Field) Setup RO11 Function RO10 Function
Reg[1041] – User (Field) Setup Field Setup Pass Code – Char 0 RO12 Function
Reg[1042] – User (Field) Setup Field Setup Pass Code – Char 2 Field Setup Pass Code – Char 1
Reg[1043] – User (Field) Setup Max Close Torque (0 – 100%) Max Open Torque (0 – 100%)
Reg[1044] – User (Field) Setup Tag ID – Char 1 Tag ID – Char 0
Reg[1045] – User (Field) Setup Tag ID – Char 3 Tag ID – Char 2
Reg[1046] – User (Field) Setup Tag ID – Char 5 Tag ID – Char 4