User`s guide
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 111
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.4.7. TEC2000 Memory Map … Table for Coils & Inputs
Register BIT 15 BIT 14 BIT 13 BIT 12 BIT 11 BIT 10 BIT 9 BIT 8 BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0
Alarm …
Unit
STOP
Command
Active
CLOSE
Command
Active
Open
Command
Active
SETUP
Mode
Selected
REMOTE
Mode
Selected
STOP
Mode
Selected
LOCAL
Mode
Selected
Alarm …
TSC (Close)
Alarm …
TSO (Open)
Valve is
Closing
Valve is
Opening
LSB is
Tripped
LSA is
Tripped
LSC is
Tripped
LSO is
Tripped
1000
(inputs)
RO 1015
RO 1014 RO 1013 RO 1012 RO 1011 RO 1010 RO 1009 RO 1008
RO 1015 RO 1014
RO 1013 RO 1012 RO 1011 RO 1010 RO 1009 RO 1008
Alarm …
Low
Battery
Alarm …
Valve
Stalled
Alarm …
Over
Torque
Valve is
Moving
COM 2
Alarm
COM 1
Alarm
Alarm …
System
Service
Required
Alarm …
Lost
Control
Signal
Alarm …
Any Non-
Hardwired
ESD
Alarm …
Hardwired
ESD
Alarm …
Close
Inhibit
Alarm …
Open
Inhibit
Alarm …
Motor
Overload
Alarm …
Lost
Phase
Alarm …
Lost
Control
Voltage
Signal
Alarm …
Valve
Drift
1001
(inputs)
RO 1031 RO 1030 RO 1029
RO 1028
RO 1027 RO 1026 RO 1025 RO 1024 RO 1031 RO 1030 RO 1029
RO 1028
RO 1027 RO 1026 RO 1025 RO 1024
Sleep
Mode
Active
Emergency
STOP
Signal
Status
100% CW
Toque
Signal
Status
100% CCW
Torque
Signal
Status
Operating
Inhibit
Signal
Status
Torque
Inhibit
Signal
Status
AIN2
Signal
Fault
AIN1
Signal
Fault
AUX Close
Contact
Engaged
AUX Open
Contact
Engaged
Digital Input
#6 State
Digital Input
#5 State
Digital Input
#4 State
Digital Input
#3 State
Digital Input
#2 State
Digital Input
#1 State
1002
(inputs)
RO 1047 RO 1046 RO 1045 RO 1044 RO 1043 RO 1042 RO 1041 RO 1040 RO 1047 RO 1046 RO 1045 RO 1044 RO 1043 RO 1042 RO 1041 RO 1040
Limits are
NOT Set
Indicator
Alarm …
CCM Link
Lost to
APD
Alarm …
APD
Failed
Alarm …
Actuator
Rotation
Fault
Alarm …
CCM Link
Lost to
ACM
Alarm …
ACM
Failed
Alarm …
EFM
Signal
Status
Alarm …
Config
Error
Alarm …
CCM Link
Lost to
RDM2
Alarm …
RDM2
Failed
Alarm …
CCM Link
Lost to
RDM1
Alarm …
RDM1
Failed
Alarm …
CCM Link
Lost to
LDM
Alarm …
LDM
Failed
CCM Status
(bit-2 of 2)
CCM Status
(bit-1 of 2)
1003
(inputs)
RO 1063 RO 1062 RO 1061 RO 1060 RO 1059 RO 1058 RO 1057 RO 1056 RO 1063 RO 1062 RO 1061 RO 1060 RO 1059 RO 1058 RO 1057 RO 1056
Rmt Cmd -
Enter
ESD
CCM CPU
Has reset
Reserved
NO-OP
Reserved
NO-OP
RO5 CMD
&
RO5 Status
SO8 CMD
&
SO8 Status
SO7 CMD
&
SO7 Status
SO6 CMD
&
SO6 Status
RO12 CMD
&
Status
RO11 CMD
&
Status
RO10 CMD
&
Status
RO9 CMD
&
Status
RO4 CMD
&
Status
RO3 CMD
&
Status
RO2 CMD
&
Status
RO1 CMD
&
Status
1004
(coils)
R/W 1015
R/W 1014
R/W 1013 R/W 1012 R/W 1011 R/W 1010 R/W 1009 R/W 1008 R/W 1015
R/W 1014
R/W 1013 R/W 1012 R/W 1011 R/W 1010 R/W 1009 R/W 1008
CMD –
Load Field
Setup Defaults
CMD –
STOP
Valve
CMD –
CLOSE
Valve
CMD –
OPEN
Valve
CMD - enter
SETUP
mode
COM2
Fault
Indicator
COM1
Fault
Indicator
AIN2
Fault
Indicator
AIN1
Fault
Indicator
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
1005
(coils)
R/W 1031 R/W 1030 R/W 1029 R/W 1028 R/W 1027
R/W 1026 R/W 1025 R/W 1024
R/W 1031
R/W 1030 R/W 1029 R/W 1028 R/W 1027
R/W 1026 R/W 1025 R/W 1024
CMD –
Clear
Alarm Log
Reserved -
No write
Access
CMD –
Archive
Torque
Profile
Reserved -
No write
Access
Reserved -
No write
Access
Reserved -
No write
Access
Reserved -
No write
Access
Reserved -
No write
Access
CMD –
Clear
Limits
CMD –
Save Travel
Limits
CMD –
Accept
Port C Limit
CMD –
Accept
OPEN Limit
Port B Limit
CMD –
Accept
Close Limit
Port A Limit
CMD – Clear
All
Archives
CMD – Clear
All Logs &
Profile
CMD – Load
Factory
Defaults
1006
(coils)
R/W 1047 RO 1046 R/W 1045 RO 1044 RO 1043 RO 1042 RO 1041 RO 1040 R/W 1047 RO 1046 R/W 1045 RO 1044 RO 1043 RO 1042 RO 1041 RO 1040
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Reserved
NO-OP
Alternate
Language
Selected
COM 2
Alarm
Enable
COM1
Alarm
Enable
Reserved
NO-OP
APD Type
Line (Motor)
Frequency
(bit 2 of 2)
Line (Motor)
Frequency
(bit 1 of 2)
3-Phase
Starter
Type
(bit 2 of 2)
Starter
Type
(bit 1 of 2)
Multi-Turn
Valve
Installation
1007
(coils)
R/W 1063 R/W 1062 R/W 1061 R/W 1060 R/W 1059
R/W 1058 R/W 1057 R/W 1056
R/W 1063 R/W 1062 R/W 1061 R/W 1060 R/W 1059
R/W 1058 R/W 1057 R/W 1056
Setpoint
Source
(if AIN control)
Enable
Open
Torque Back
Seating
Enable
Close
Torque
Seating
Enable
Local
Seal-In
Enable
Remote
Seal-In
Enable
Torque Retry
RDM1
Installed
RDM2
Installed
ESD
Override –
LOCAL
Mode Ctl
ESD
Override –
STOP
Mode Ctl
ESD
Override –
Inhibits
ESD
Override –
Torque
Alarm
ARM is
Installed
Enable
Open Cycle
Timer
Enable
Close Cycle
Timer
Enable
Anti-Water
Hammer
1008
(coils)
R/W 1079 R/W 1078 R/W 1077 R/W 1076 R/W 1075 R/W 1074 R/W 1073 R/W 1072 R/W 1079 R/W 1078 R/W 1077 R/W 1076 R/W 1075 R/W 1074 R/W 1073 R/W 1072
Controlinc
ACM
Installed
Futronic
ACM
Installed
AO2
Source
(bit 1 of 2)
AO1
Source
(bit 2 of 2)
AO1
Source
(bit 1 of 2)
Multi-Port
Valve
Installation
Drive Sleeve
Closes in
CW direction
Enable
Multi-Port
Synch
Enable
Inhibit
Open Valve
Operations
Enable
Inhibit
Close Valve
Operations
ESD Trigger
on Hardwired
(LOCAL)
ESD
ESD Trigger
on Remote
Host
Command
ESD Trigger
on Loss of
Control
ESD
Action
(bit 2 of 2)
ESD
Action
(bit 1 of 2)
ESD Override
– Thermal
Overload
Alarm
1009
(coils)
R/W 1095 R/W 1094 R/W 1093 R/W 1092 R/W 1091 R/W 1090 R/W 1089 R/W 1088 R/W 1095 R/W 1094 R/W 1093 R/W 1092 R/W 1091 R/W 1090 R/W 1089 R/W 1088
Worm Gear is
LH
Set LED …
Open – RD
Close - GR
Reserved
NO-OP
Motor
Rotation is
Electrically
Reversed
Enable
Battery
Alarm
AO2
Source
(bit 2 of 2)
Enable
AIN2 Alarm
on Lost
Signal
Enable
AIN1 Alarm
on Lost
Signal
Action if Lost
Control
Signal
(bit 2 of 2)l
Action if Lost
Control
Signal
(bit 1 of 2)l
Reserved
NO-OP
Analog
Output
“Close”
Polarity
Analog
Input
“Close”
Polarity
Control
Mode
(bit 3 of 3)
Control
Mode
(bit 2 of 3)
Control
Mode
(bit 1 of 3)
1010
(coils)
R/W 1111 R/W 1110
R/W 1109
R/W 1108 R/W 1107 R/W 1106 R/W 1105 R/W 1104 R/W 1111 R/W 1110
R/W 1109
R/W 1108 R/W 1107 R/W 1106 R/W 1105 R/W 1104