User`s guide

Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 110
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
320B
Holding
Register
#
Description
Range
(Remote
Interface)
Increment
(Remote
Interface)
45 Open coast distance 0 – 4095 Analog counts
46 Close coast distance 0 – 4095 Analog counts
47 Reserved ----------- ----------
48 Current torque at 10% open while opening valve 0 – 4095 Analog counts
49 Current torque at 20% open while opening valve 0 – 4095 Analog counts
50 Current torque at 30% open while opening valve 0 – 4095 Analog counts
51 Current torque at 40% open while opening valve 0 – 4095 Analog counts
52 Current torque at 50% open while opening valve 0 – 4095 Analog counts
53 Current torque at 60% open while opening valve 0 – 4095 Analog counts
54 Current torque at 70% open while opening valve 0 – 4095 Analog counts
55 Current torque at 80% open while opening valve 0 – 4095 Analog counts
56 Current torque at 90% open while opening valve 0 – 4095 Analog counts
57 Archived torque at 10% open while opening valve … EEPROM 0 – 4095 Analog counts
58 Archived torque at 20% open while opening valve … EEPROM 0 – 4095 Analog counts
59 Archived torque at 30% open while opening valve … EEPROM 0 – 4095 Analog counts
60 Archived torque at 44% open while opening valve … EEPROM 0 – 4095 Analog counts
61 Archived torque at 50% open while opening valve … EEPROM 0 – 4095 Analog counts
62 Archived torque at 60% open while opening valve … EEPROM 0 – 4095 Analog counts
63 Archived torque at 70% open while opening valve … EEPROM 0 – 4095 Analog counts
64 Archived torque at 80% open while opening valve … EEPROM 0 – 4095 Analog counts
65 Archived torque at 90% open while opening valve … EEPROM 0 – 4095 Analog counts
66 User Digital Input #1 Totalizer (accumulator) 0 – 65535 Input strobes
67 User Digital Input #2 Totalizer (accumulator) 0 – 65535 Input strobes
68 Loss-of-COM alarm delay time. 1000 – 65535 0.001 second
69 Valve Stall delay time 400 – 65535 0.001 second
70 Travel time for 1% travel
100 – 36000 0.001 second
71 Reserved --- ---
72 – 99
Not used … returns an error if accessed. --- ---
100 MFG ID + Network Address --- ---