User`s guide

Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 106
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.4.4. 320A Memory Map … Addressable Holding Registers (Version 2.0)
320A
Holding
Register
#
Description
00 (coils 0 15) … Mode / Command / Output Coils
01 (coils 16 31) … Valve status coils
02 (coils 32 47) … Configuration coils
03 (coils 48 63) … Configuration coils
04 (coils 64 79) … Configuration coils
05 (inputs 0 15) … Discrete inputs
06 (inputs 16 31) … Valve Status inputs
07
Valve Position
08 (inputs 32 47) … Valve Status inputs
09 Valve status (inputs 16 31) … identical to register [6]
10 Analog output register (DAC)
11 Valve position setpoint
12 RESERVED
13 Valve position … 0 100% in 0.1% increments
14
AIN0 … Analog input #0 … position indicator
This value indicates the actual position of the actuator.
15 AIN1 … Analog input #1 … Torque indicator pot
16 AIN2 … Analog input #2 … User analog input #1
17 AIN3 … Analog input #3 … User analog input #2
18 Water hammer setpoint
19 Modulation delay time
20 ESD delay timer
21 Position bandwidth
22 Speed bandwidth
23
RESERVED
24 AIN1 (Torque Pot) ZERO calibration scaling factor
25 AIN1 (Torque Pot) SPAN calibration scaling factor
26 AIN2 (User AIN #1) ZERO calibration scaling factor
27 AIN2 (User AIN #1) SPAN calibration scaling factor
28 AIN3 (User AIN #2) ZERO calibration scaling factor
29 AIN3 (User AIN #2) SPAN calibration scaling factor
30 Analog output ZERO calibration scaling factor
31 Analog output SPAN calibration scaling factor
32 LSA setpoint
33 LSB setpoint
34 Valve CLOSE Duty Cycle Timer – ON Time
35 Valve CLOSE Duty Cycle Timer – OFF Time
36 Valve OPEN Duty Cycle Timer – ON Time
37 Valve OPEN Duty Cycle Timer – OFF Time
38 COM1 baud rate
39 COM1 response delay
40 COM2 baud rate
41 COM2 response delay
42 Passcode characters 1&2 … (1 LSB) (2 MSB)
43 Passcode characters 3&4 … (3 LSB) (4 MSB)
44 Software Version ID
45 RESERVED