User`s guide

Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 6
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
1.4. EIM Equipment Compatibility
The 1746-C is compatible with the following EIM equipment:
320A … version 1.17 and later.
320B … all
TEC2000 … all
Other points:
The 1746-C derives the system type of each actuator during the diagnostic scan and stores the
results in table [18].
The 1746-C derives the firmware Version ID for the 320A & 320B systems during the diagnostic
scan and stores the results in table [19].
Since the TEC2000 system has several micro-controllers with firmware, a special request must
be made to them to derive the firmware version ID for each controller in the unit.
The SSR bit is only checked and set on 320A actuators.
Note: For maximum compatibility with the TEC2000 systems, it is recommended that you enable
monitoring the TEC2000 Status Inputs (tables [21-24]). This way, you can ensure you have all
critical status information for any TEC2000 system on the network. For more information,
refer to the section on Tables [21-24].
Note: This document references the addressable memory ranges (“Memory Maps”) of several EIM
actuators (ex: M2CP–320B, TEC2000). This is only for the reader’s convenience. The
specific details in the memory maps are only correct as of the date this manual was published.
Therefore, to ensure you have the most current memory information, please refer to the
technical information for that particular actuator.
1.5. Firmware
The firmware is a “driver program” which is a compiled application program (not an interpreted one). It
is loaded and stored in the module's 32K EEPROM (A-B P/N 1747-M2). The user is required to
provide configuration information from the PLC Relay Ladder Logic (RLL) for each specific application
(the RLL must load table [0] with appropriate configuration information).