6.2.6. Bringing Units On-Line After a Power Cycle
ACTUATOR POWER CYCLE
If you cycle power on the actuators, the 1746-C will indicate that the actuators are off line and it will only
bring them back on line during the next diagnostic scan.
COMPLETE POWER CYCLE
When there is a complete power failure to the actuators and Master Station at same time (if power
cycles on the entire system – actuators, PLC & 1746-C), “what happens when” depends upon what
system comes back on line first.
If an actuator comes on line before the 1746-C is out of reset, then the 1746-C will see it when it
performs its network check as it comes out of reset (it will be "on-line"). If the 1746-C comes up
before an actuator, then that actuator will not get "on-line with the 1746-C" until the next diagnostic
scan is performed.
GENERAL
Usually, if any actuators do not start communicating with the 1746-C after it performs its diagnostic
scan, the places to look are outside the 1746-C (the actuators, the interconnecting network, …).