Datasheet

Modbus TCP Communication HIMA H41q/H51q
Emerson DeltaV
5
Note 1:
Variables defined as Import/Export use separate addresses for reading and for
writing, according to Modbus conventions. Thus an Import/Export variable reserves
twice as much memory space as an equivalent Export or Import variable.
Import/Export addresses must be projected in both (read and write) memory areas.
Boolean variables can be made an event by checking the Event check box beneath the “Event
handling” tab. Like with BUSCOM variables you can also declare specific addresses under which the
event should be communicated.
Note 2:
If you define a spare range of communication addresses it is not necessary to
download the H41q/H51q when adding new communication variables or events
instead you can proceed with a reload of the PES. You can achieve this by inserting a
dummy communication variable or event some addresses ahead of the actually used
range.
2.3. Configuration of DeltaV Hard- and Software
The necessary configuration of the DeltaV DCS for Modbus TCP communication consists of the
configuration of the ethernet communication module Mynah VIM, the simulated DeltaV serial cards
and of the take-over of the communicated data in the application software of the DeltaV control
modules.
2.3.1 VIM Configuration
The Mynah VIMs are installed next to the DeltaV 2-wide controller carrier on the left side. They are
mounted, together with a standard DeltaV power supply, on a separate 2-wide controller carrier.
Note 3:
If necessary due to mounting space restrictions the 2-wide DeltaV controller and VIM
carriers can be separated from the 8-wide DeltaV IO carriers by using extender sets
which separate the carriers by means of special signal cables and extender modules.
Two standard ethernet Layer 2 switches are used as network nodes for Modbus TCP communication
in the primary and secondary network. These switches are also certified for use with HIMA´s safe
communication via safeethernet to other H41q/H51q PES and they can also be used if additional
OPC DA or OPC A&E Servers need to be used.
Note 4:
The Mynah VIMs require the use of two switches as coupling devices for redundant
connections because the VIMs need a cross link cable between these switches
(marked in red in Figure 2.1) to carry out their redundancy replication. Also for a
redundant direct point-to-point connection (one DeltaV controller communicating to
one HIMA PES) crossed network cables cannot be used. Instead two switches and a
cross link cable between them are required.