Datasheet

Modbus TCP Communication HIMA H41q/H51q ↔
↔↔
↔ Emerson DeltaV
2
2. Described Configuration
2.1. Detailed System Layout
The detailed hardware layout on which this Application Note is based is shown in Figure 2.1.
Figure 2.1: Network Overview for H41q/H51q ↔
↔↔
↔ DeltaV Modbus TCP Communication
The used hardware and software components are:
Hardware: Software:
H41q/H51q PES ELOP II Engineering Software
F 8627X Ethernet communication module ELOP II license dongle
DeltaV MD Controller DeltaV Automation Software
DeltaV Professional Plus Workstation DeltaV System licenses
Ethernet Cat. 5 network cables DeltaV serial port licenses
Industrial Ethernet Switches
For detailed information about the explicitly tested hardware, software, firmware and Operating
Systems refer to the Communication Test Report (see [6]).
2.2. Configuration of H41q/H51q Hard- and Software
The necessary configuration of an H41q/H51q PES for Modbus TCP communication consists of the
configuration of the ethernet communication module F 8627X on the hardware side and of setting the
IP address and defining communication variables in the application software.
2.2.1 Hardware Configuration
The hardware of HIMA safety systems can consist of one or several H41q/H51q safety PESs. The
necessary hardware configuration for communication is the same for all PESs and simply consists of
setting the Bus Station Number (BSN) of all CPUs and configuring the F 8627X ethernet
communication module. All settings are made via DIP switches when the module is removed from the
rack.