Datasheet

Modbus TCP Communication HIMA H41q/H51q
Emerson DeltaV
6
The configuration of the VIM is carried out with
Mynah’s VIMNet Explorer” which is not necessary for
operation of the VIMs and can therefore be installed on
a
separate computer which needn’t be permanently
connected to the communication network. When the
VIM needs to be configured initially or for expansion of
available Modbus TCP devices the VIMNet Explorer
must be connected via a Network Interface Card (NIC)
which must reside in the same network range like the
VIM itself. I.e. VIM host address 192.168.0.241 is only
accessible from 192.168.0.x when the NICs netmask is
255.255.255.0. Keep this fact in mind when you
encounter connection problems between VIMNet
Explorer and the VIM.
When the VIMNet Explorer is initially started the tree
consists just of the area “VIMNETand the underlying
“I/O Net” similar to the DeltaV Explorer’s view. The
initial configuration of the VIM to be ready for Modbus
TCP communication requires the following seven
steps:
Figure 2.4: VIMNet Explorer Tree
1. Add a controller to which the VIM should be assigned using the context menu of I/O Net. Use the
same name like in DeltaV Explorer to simplify identification of corresponding structures.
2. Add a VIM below the newly created controller using the controller’s context menu.
3. Configure the VIM’s properties according to Figure 2.5 to be of type “I/O VIM Modbus TCP”,
select redundancy if necessary. Enter the appropriate IP addresses and subnet masks.
Figure 2.5: VIM Properties
4. Add a new Modbus device below the desired serial card. The device must be defined in VIMNet
Explorer and DeltaV Explorer whereas the communication data (datasets) are only defined in the
DeltaV Explorer.
5. Configure the device properties according to Figure 2.6 with Device Address and primary and
secondary IP address of the H41q/H51q. The used Port should be set to 502 and the Number of
Simultaneous Messages must be set to 1. For a simplex connection you need to set to “Simplex
Device” and use just one IP address. A redundant connection can be set to “Redundancy with
Switching IP” (which means the active VIM stays active when a connection failure to it’s active
slave occurs and it just uses the secondary IP address via the cross link cable) or to “Redundancy
with No Switching IP” (which in turn means the master also switches when a connection failure to
it’s active slave occurs; this is the normal behaviour of the DeltaV redundant serial card).