Data Sheet
Bulletin 71.4:MR98
10
Typical relieving capacities in lbs per hour and kilogram
per hour of saturated steam are shown in Tables 9, 14
and 19.
Tables 7, 8, 12, 13, 17 and 18 give relieving capacities in
U.S. gallons per minute and in liters per minute of water.
Sizing
Determine Flow Rates for units used as differential relief
valves as follows:
Air and Steam Service
When the Capacity Information section do not cover
the actual service conditions, it will be necessary to
calculate the ow rate available from the relief valve.
Step 1.
From the Capacity Information section determine a
ow rate using the closest available data for setpoint
and build-up. With this information, calculate a ow
coefcient using the following:
Equation 1:
Q
C
g
=
P
1a
SIN
DEG
520
GT
)
)
P
1a
∆P
3417
C
1
C
g
= Calculated ow coefcient
Q
= Flow rate from tables (SCFH)
P
1a
= Inlet pressure from table (set pressure and
build-up) converted to absolute pressure
G = Specic gravity
T = Absolute temperature of gas at inlet,
°Rankine = °F + 460
P
1
= Absolute inlet pressure, psia = psig + 14.7
C
1
= See specications section
∆P = P
1
- P
2
, psid
Calculate the C
g
coefcient for the setting and build-up
nearest to the desired service conditions within the
selected spring range. Then use this C
g
to calculate
the approximate ow available for the actual setpoint
and build-up desired. Available C
g
will vary based
upon setpoint, differential pressure, build-up and
spring range.
Step 2.
Calculate the actual ow rate available using the
coefcient from Step 1 and the actual inlet pressure
(setpoint plus build-up) and actual outlet pressure
(if not atmospheric).
Equation 2:
Q
SCFH
=
C
g
P
1a
SIN
DEG
520
GT
)
)
P
1a
∆P
3417
C
1
Liquid Sizing for Liquids Other than Water
Step 1.
Determine C
v
at build-up conditions of application.
C
v
=
Q
∆P
Q = Flow in GPM from capacity tables
∆P = Pressure drop in psi (setpoint and build-up)
C
v
= Valve sizing coefcient
Step 2.
To determine ow rate for liquids other than
water or ow rate for differential relief service:
Q = C
v
∆P/G
G = Specic gravity of uid
Maximum Allowable Pressure Drop for
Liquid Service
Pressure drops in excess of allowable will result in
choked ow and possible cavitation damage.
To determine maximum allowable pressure drop
for water:
∆P(allow) = K
m
(P
1
)
∆P = Valve differential - psi
K
m
= Valve recovery coefcient from table
P
1
= Valve inlet pressure psig
To determine maximum allowable pressure drop for
uids other than water, see Fisher
®
Sizing Program.
Installation
These valves may be installed in any position, as long
as ow will be in the same direction as that of the
arrow cast on the body. For dimensional information
see Figure 4.
Emerson Process Management Regulator Technologies,
Inc. (Emerson™), provides an instruction manual
with every valves shipped. Refer to this for complete
installation, operation and maintenance instructions.
Included is a complete listing of individual parts and
recommended spare parts.










