User manual

System Configuration
8
3.2 Service Terminal
Refer to Accessing the Configuration Port on page 5 for details
on accessing the service terminal / configuration port.
The default service terminal communication parameters are:
9600 bps
•No parity
8 data bits
1 stop bit
Flow Control: None
After connecting to the OpenComms NIC-485, press the space bar or
Enter key to activate the service terminal session. If no response is
apparent and you have verified connectivity, cycle power on the
Open-Comms NIC-485 and the service terminal sessions should
appear automatically.
!
CAUTION
Cycling power on either the 7200 or the HiPulse UPS is not
recommended unless the unit is in bypass mode. Consult the
UPS user manual for further instructions.
Table 3 Service terminal navigation
Main Menu
1.0 Firmware Updates
1.1 Initiate XMODEM Update
2.0 Factory Settings
2.1 Reset to Factory Defaults
2.2 Manufacture Date (Read Only)
2.3 Serial Number (Read Only)
2.4 Boot Version (Read Only)
2.5 App Version (Read Only)
2.6 Hardware Version (Read Only)
3.0 Modbus Server
3.1 Control
3.2 Server ID
3.3 Communication Rate (Read Only)
q Quit and abort changes
x Exit and save