Specifications

STARTUP and OPERATION
4.8 Viewing
µ
CEM Data with an external PC Web Browser
The MicroCEM internal log files may be accessed using a user PC or laptop with a web
browser that has access to the µCEM over a LAN, serial port connection (PPP) or
Dialup Connection (RAS). The µCEM has Window CE Web Server installed and
provides a Web-based interface to select and download the Data-Log files. The
downloaded Data-Log files will be in a CSV (comma delineated ASCII) format. The log
files may also be viewed as a web page in a tabular format.
1. Connect user PC or laptop to the MicroCEM via Ethernet LAN circular connector
located on J4 connector. The Ethernet cable can then be routed to the users
Ethernet hub where as many PC’s as desired can access the MicroCEM Web
Browser. Customer may also choose to connect the cable directly to the
Ethernet port located on the MicroCEMs PC104 PCB which is internal to the
MicroCEM. Note that a crossover type Ethernet cable must be used if a hub is
not utilized.
2. The user PC or laptop must have the same IP address as the MicroCEM or the
MicroCEM IP address can be changed to the users desired IP address.
Standard IP address of the MicroCEM is: 192.168.1.92
3. Once the IP addresses are matched the user can simply open internet explorer
on their computer and type is the MicroCEMs IP address.
4. Once entered a user ID and password must be entered. These are the identical
user ID and password as input into the administration menus.
5. Once entered the user can then access all pages as specified in section 4.7.
4.8.1 Real-Time Page
The Real-Time page provides a real-time display of the emission values and emission
statuses. The display is refreshed every 10 seconds.
Rosemount Analytical µCEM Continuous Analyzer Transmitter 4-1