Instruction manual

232 Using Modbus
®
Protocol with Micro Motion
®
Transmitters
Troubleshooting continued
30422 Bit #0 API: Temperature outside standard range Ö Ö
Bit #1 API: Line density outside standard range
Ö Ö
Bit #2 Line temperature sensor out of range
Ö Ö Ö
Bit #3 Meter temperature sensor out of range
Ö Ö Ö
Bit #4 Flow direction (1 = reverse, 0 = forward or zero flow)
Ö Ö Ö
Bit #5 Not used
Bit #6 Not used
Bit #7 Not used
Bit #8 Not used
Bit #9 Transmitter not configured
Ö Ö Ö
Bit #10 (E)EPROM checksum error
Ö Ö
Bit #11 RAM test error Ö Ö
Bit #12 Invalid/unrecognized sensor type
Ö Ö Ö
Bit #13 (E)EPROM database corrupt, core processor
Ö Ö Ö
Bit #14 (E)EPROM powerdown totals corrupt, core processor
Ö Ö Ö
Bit #15 (E)EPROM program corrupt, core processor
Ö Ö Ö
30423 Bit #0 Boot sector fault, core processor Ö Ö Ö
Bit #1 Software upgrade needed, core processor Ö Ö
Bit #2 Frequency output fixed
Ö Ö
Bit #3 Not used
Bit #4 Discrete output #1 status
Ö
1
Bit #5 Discrete output #2 status
Ö
2
Bit #6 T-Series D3 calibration in progress Ö Ö Ö
Bit #7 T-Series D4 calibration in progress Ö Ö Ö
Bit #8 Not used
Bit #9 Not used
Bit #10 Temperature slope calibration in progress
Ö Ö Ö
Bit #11 Temperature offset calibration in progress
Ö Ö Ö
Bit #12 Flowing density calibration in progress Ö Ö Ö
Bit #13 High-density calibration in progress Ö Ö Ö
Bit #14 Low-density calibration in progress
Ö Ö Ö
Bit #15 Flowmeter zeroing in progress
Ö Ö Ö
Table 23-2. Diagnostic input registers continued
Input
register Description MVDSolo
Series
1000
Series
2000 RFT9739