Installation Manual
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
[91 of 149]
12. The system responds with...
Condition Description: current info
Condition Description:
13. This parameter applies only to TL1 commands/messages.
Type a user-defined text message (40 characters
maximum) which provides a detailed description of this
alarm, event, or condition. Then press
ENTER
. May also
be used to describe any action to be taken as a result of
the condition. All printable ASCII characters are valid
except for the percent sign (%), double quotes ("), and the
backslash (\).
14. The system responds with...
Notification Code: current info
Notification Code:
15. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes the
severity of this alarm or event condition, then press
ENTER
.
CR - critical alarm NA - not alarmed
MJ - major alarm NR - not reported when event occurs
MN - minor alarm
16. The system responds with...
Service Effect Code: current info
Service Effect Code:
17. This parameter applies only to TL1 commands/messages.
Type one of the following codes which describes how this
alarm or event affects service, then press
ENTER
.
SA = service-affecting condition, immediate action
required
NSA = nonservice-affecting condition, action required
18. The system responds with...
Alarm Condition: current info
Alarm Condition (CC or CO):
19. Type the characters
CC
or
CO
which represents the
condition required to activate an alarm, then press
ENTER
.
20. The system responds with...
Alarm Class Number:
21. Type the desired alarm class number associated with this
channel, then press
ENTER
. Alarm classes are specified
with the numbers 0 through 8, with 0 representing no
alarm class.
22. The system responds with...
Off Delay Time: current info
Off Delay Time:
23. Type the required alarm off delay time period* and a
modifier*, then press
ENTER
. The off delay time is the
amount of seconds that an alarm condition must cease
before the system recognizes that the alarm condition
ceased.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
Note:
The timing involved in the operation of the rectifier
sequencing feature will be affected if the alarm delay
attributes for the binary channels selected to control
the sequencer are configured. Configuring the “On
Delay” or “Off Delay” for the AC Fail / Transfer input
or Standby On / Proper Operate input will postpone
detection (signals may have already been detected
by the transfer device) of an AC Failure or Proper
Operate signal by the system rectifier sequencing
software.
24. The system responds with...
On Delay Time: current info
On Delay Time:
25. Type the required alarm on delay time period* and a
modifier*, then press
ENTER
. The on delay time is the
amount of seconds that an alarm condition must exist
before the system recognizes it as an alarm condition.
* Enter a valid value (0-9999) then the modifier (s for
seconds, m for minutes, h for hours). If no modifier
entered, modifier defaults to seconds.
Note:
The timing involved in the operation of the rectifier
sequencing feature will be affected if the alarm delay
attributes for the binary channels selected to control
the sequencer are configured. Configuring the “On
Delay” or “Off Delay” for the AC Fail / Transfer input
or Standby On / Proper Operate input will postpone
detection (signals may have already been detected
by the transfer device) of an AC Failure or Proper
Operate signal by the system rectifier sequencing
software.
26. The system responds with...
Save changes (Y or N):
27. Type
Y
if the above entered data is to be saved in the
current binary channel configuration and
N
if not, then
press
ENTER
.
28. The system will display the second binary channel
configuration. Enter the required data for each binary
channel as described above until the system displays the